minor: close the six gaps FTW's site test patched around - #8

Merged
frahlg merged 9 commits into
mainfrom
fix/ftw-rig-gaps
Oct 23, 2026
Merged

frahlg merged 9 commits into
mainfrom
fix/ftw-rig-gaps

Conversation

@frahlg

@frahlg frahlg commented Oct 22, 2026 •

Copy link
Copy Markdown
Member

FTW now tests every change to its core against this simulator: a Sungrow hybrid on Modbus, an SDM630 site meter behind an IEC gG fuse and OCPP 1.6 chargers. The first rig (21 October, outside any repo) had to patch around six gaps. This PR closes them, one commit each, each with a test, so the rig in srcfl/ftw needs no workarounds. Paired with srcfl/ftw#1797, which pins this branch's commit (1419f1b).

Gap Fix Test
The OCPP charger dialled without credentials; FTW requires Basic auth, and the WebSocket dialer refuses user:pass@ in a URL user:password in ocpp_url goes out as an Authorization header; logs show xxxxx TestClientSendsBasicAuthFromURL, TestClientWithoutCredentialsSendsNoAuth
A car plugged in before the charger reached its Central System lost its StartTransaction StartTransaction and StopTransaction wait in a queue while offline and go out, in order, after the next accepted BootNotification TestStartTransactionWaitsForTheConnection
No command delay: every profile applied at once profile_delay_s in POST /api/simulators/{id}/config: Accepted at once, applied that much later, in order, like a cloud charger. Invalid profiles are still refused at once TestProfileDelayAcceptsAtOnceAndAppliesLater, TestNoProfileDelayAppliesAtOnce
Power always spread over three phases, also under numberPhases: 1 A charger with ConnectorSwitch3to1PhaseSupported draws a 1-phase profile on L1, at most its rated current. It reports phasePowers and per-phase currents, and the site meter takes chargers per phase instead of through the phase factors TestOnePhaseProfileDrawsOnL1, TestOnePhaseDrawIsCappedAtRatedCurrent, TestSiteMeterPutsOnePhaseChargerOnL1
Sungrow defaults in the wrong scale: an SH10RT came up as 100 kW with 500 kW battery limits Defaults are engineering values: 10 kW (5000), 5 kW (33046/33047), in the register set, the global defaults and the sungrow-hybrid and residential-5kw profiles TestSungrowHybridDefaultsAreAnSH10RT (fails on main)
EMS writes to 13049–13051 stored but never applied ems_control: true makes the battery do what a real SH does: forced mode (13049 = 2) follows 13050/13051, any other mode runs self-consumption against the site meter. It answers after the model's command_response_s (2 s for sungrow-hybrid), keeps 33046/33047 and the SoC limits 13057/13058, and writes the power-flow flags (13000) the Lua driver signs by TestEMSForcedModeDrivesTheBattery, TestEMSSelfConsumptionCancelsTheMeter, TestEMSKeepsTheSoCLimits, TestEMSResponseTime, TestEMSWritesIgnoredWithoutEMSControl

The split: what this repo has and what FTW's rig added

The house lives here; srcfl/ftw keeps only its scenario pack (which cases, FTW's config, criteria read from FTW's API), the pinned simulator commit, make siterig and a runner on its own machine. This is the first of three PRs; #9 and the headless-run PR follow.

Piece Here before What FTW's first rig (21 Oct) did about it Where it is after these PRs
Site with load per phase, static load scenario yes used it unchanged
24 h load scenarios (scenarios.go), weather scenarios, generators yes not used unchanged
Serial numbers per protocol (runtime.go) yes used them unchanged
IEC 60269 fuse per phase (fuse.go) yes, in package main used it package fuse (#9), for FTW's sitesim to import
Sungrow register defaults wrong scale (100 kW, 500 kW) wrote 10 / 5 / 5 kW fixed here
EMS writes 13049–13051 stored, never applied a responder applied them after 2 s ems_control + command_response_s here
OCPP charger dialling a Central System yes, no credentials a proxy added Basic auth Basic auth from the URL here
A charger that applies profiles late no the proxy held them 60–120 s command_response_s here
A 1-phase profile on L1 no, always three phases a phase model in the rig here
StartTransaction while offline lost plugged only after connect queued here
One heartbeat and meter loop per connection no, one more set per reconnect — headless-run PR
The car's own current and phases no — headless-run PR (SetCar)
A dropped charger connection no — headless-run PR (reconnect)
Building a house from a spec about 40 API calls from Python stack.py, rig.py headless-run PR (simulator run -spec)
A record of the house once a second no the rig polled the API headless-run PR (plant.jsonl)
Every OCPP frame no the proxy logged them headless-run PR (ocpp-<id>.jsonl)
Timelines and events during a run, port offsets env vars per protocol Python scripts, RIG_PORT_OFFSET headless-run PR (-port-base, /api/run/event)
Device silence, meter late or glitched, signed phase currents, a charger's own load balancer, start delay, seeded random timelines no no next PR here, planned
Site plant: scalar bus, thermal, heat pump (#6, draft) draft — compatible; see the comment in #6

Models and the driver each emulates

driver_id is the srcfl/device-drivers driver a model emulates, by file name without .lua; ocpp is FTW's own OCPP Central System. Timing and quirks live in each model's model block, so field evidence for a driver can set them later.

Profile Protocol driver_id model
sungrow-hybrid Modbus sungrow command_response_s: 2
solis-hybrid Modbus solis
solaredge Modbus solaredge
sma-tripower Modbus sma
huawei-sun2000 Modbus huawei
fronius-gen24 Modbus fronius
deye-hybrid Modbus deye
pixii-powershaper Modbus pixii
ferroamp-energyhub Modbus ferroamp_modbus
sdm630 Modbus sdm630
fronius-smart-meter Modbus fronius_smart_meter
ambibox MQTT ambibox_v2x
ocpp-charger, chargeamps-dawn OCPP 1.6 ocpp
residential-5kw, commercial-50kw, default Modbus none (generic)

command_response_s replaced the two settings this branch first added (ems_response_ms, profile_delay_s).

What changes for other users

  • ems_control is off unless set, and command_response_s is 0 except where a model says otherwise. The dashboard still sets the battery by writing the registers.
  • A charger's draw now reaches the site meter per phase. A 3-phase charger is split evenly, as with the default phase factors. A site with uneven phase factors now sees its chargers balanced.
  • New config fields are saved in the state file and listed in openapi.json and the MCP tool for /api/simulators/{id}/config.
  • go test -race ./... passes.

Overlaps

  • A local, uncommitted change elsewhere fixes the same Sungrow scale (5000, 33046, 33047); whichever lands second has a one-line conflict.
  • Draft Site simulator: thermal plant, facility presets, and live schematic #6 (site plant) models EMS setpoints inside its physical plant, only under the physical scenario. This PR keeps to the existing aggregation path and an opt-in flag, so the two can land in either order.

Not in this PR

  • The charger has no 6 A minimum and draws its offer at once. The rig does not depend on it.
  • Each reconnect of a client-mode charger started another heartbeat, MeterValues and simulation loop. Fixed in the headless-run PR, which needs reconnects.

Review fixes (Codex, 1419f1b)

Finding Fix Test
A Sungrow limit register holding 0 turned its clamp off a model with the register enforces it, 0 included TestEMSKeepsZeroPowerLimits
GetCompositeSchedule reported a one-phase draw as a third of it on three phases it uses the charger's effective phases, and a change of phases starts a period TestCompositeScheduleKeepsThePhases
A session that started and ended offline was stopped under its local id the start's answer maps the local id for the queued stop TestQueuedStopNamesTheAssignedTransaction

Rebased on main with #9 (the thermal fuse) on 23 October. Nothing in this PR changed; #10 and #11 follow on top.

🤖 Generated with Claude Code

@chatgpt-codex-connector

chatgpt-codex-connector Bot commented Oct 22, 2026 •

Copy link
Copy Markdown

Codex Review Summary

This comment shows the latest Codex review activity on this pull request.

Review Status Commit Review trigger
📝 Code Review ✅ Completed 2026-10-22T05:27:02.601169Z 1419f1b PR opened
ℹ️ About Codex in GitHub

Your team has set up Codex to review pull requests in this repo. Reviews are triggered when you

  • Open a pull request for review
  • Mark a draft as ready
  • Comment "@codex review" or "@codex security review".

Codex reacts with 👀 while any review is running, comments if it has suggestions, and reacts with 👍 once all reviews finish with no findings.

@chatgpt-codex-connector chatgpt-codex-connector Bot left a comment

Copy link
Copy Markdown

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

💡 Codex Review

Here are some automated review suggestions for this pull request.

Reviewed commit: 1419f1b862

ℹ️ About Codex in GitHub

Your team has set up Codex to review pull requests in this repo. Reviews are triggered when you

  • Open a pull request for review
  • Mark a draft as ready
  • Comment "@codex review".

If Codex has suggestions, it will comment; otherwise it will react with 👍.

Codex can also answer questions or update the PR. Try commenting "@codex address that feedback".

Comment thread internal/ocpp/server.go
}

s.sendRequest(ActionStopTransaction, req)
s.sendTxRequest(ActionStopTransaction, req, nil)

Copy link
Copy Markdown

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

P2 Badge Remap queued stops to the server-assigned transaction ID

If a charging session starts and ends while offline, both messages are queued, but the StopTransaction payload retains the local transaction ID. On reconnect, StartTransaction receives the CSMS-assigned ID, while its callback cannot update the already-deleted transaction or the queued stop payload. For example, a local transaction 1 accepted as transaction 42 is subsequently stopped as transaction 1, leaving transaction 42 open at the CSMS. Preserve a per-session ID mapping and resolve queued StopTransaction IDs after the corresponding start response.

Useful? React with 👍 / 👎.

Comment thread cmd/simulator/ems.go Outdated
Comment on lines +53 to +57
if limit := getSemanticValue(sim, "max_charge_power") * 1000; limit > 0 && w > limit {
w = limit
}
if limit := getSemanticValue(sim, "max_discharge_power") * 1000; limit > 0 && w < -limit {
w = -limit

Copy link
Copy Markdown

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

P2 Badge Enforce zero-valued battery power limits

With ems_control enabled, explicitly writing zero to Sungrow's maximum charge or discharge power register disables the corresponding clamp because of the limit > 0 condition. A forced 3000 W charge therefore still draws 3000 W with max_charge_power = 0, and self-consumption can likewise discharge despite a zero discharge limit. Distinguish an absent semantic register from a present register containing zero, and enforce zero as a maximum of zero.

Useful? React with 👍 / 👎.

Comment thread internal/ocpp/server.go
Comment on lines +1392 to +1393
w, _ := s.computeEffectiveLocked(connectorId, now)
return w

Copy link
Copy Markdown

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

P2 Badge Propagate effective phases into composite schedules

For a phase-switching charger using a one-phase profile, handleGetCompositeSchedule still calls this watts-only wrapper, divides power by three phase voltages for ampere schedules, and hardcodes NumberPhases to 3 (lines 1179–1196). Consequently, a charger actually drawing 16 A on L1 reports approximately 5.3 A on three phases, so a CSMS inspecting the composite schedule receives a different per-phase load from the one now simulated. Update that caller to use computeEffectiveLocked, convert using the effective phase count, and emit phase-count changes as schedule boundaries.

Useful? React with 👍 / 👎.

frahlg and others added 8 commits October 23, 2026 07:12
A Central System that requires OCPP 1.6 security profile 1 (FTW does)
refused the simulated charger: it dialled without credentials, and the
WebSocket dialer rejects user:password inside the URL. Move them to an
Authorization header and keep the password out of the logs.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
A car plugged in before the charger had reached its Central System
started a local session whose StartTransaction was lost: sendRequest
failed and nothing kept the message. Queue StartTransaction and
StopTransaction while there is no connection and send them, in order,
after the next BootNotification is accepted.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
A cloud charger such as Easee accepts a charging profile at once and
changes its output a minute or two later. The simulated charger applied
every profile at once, so nothing could test how a Central System
copes with that. POST /api/simulators/{id}/config {"profile_delay_s": 60}
now holds accepted SetChargingProfile and ClearChargingProfile changes
for that long, in order. Invalid profiles are still refused at once.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
The simulated charger always spread its draw evenly over three phases,
also under a profile with numberPhases 1, so a site meter never saw the
one-phase load a real car puts on L1. A charger that can switch phases
(ConnectorSwitch3to1PhaseSupported) now draws a 1-phase profile on L1
only, at most its rated current per phase, and reports it per phase:
phasePowers and per-phase currents in its state and MeterValues. The
site meter takes a charger's draw per phase instead of through the
site's phase factors.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Register defaults are written through each register's scale, but the
Sungrow ones were raw register values: an SH10RT came up rated 100 kW
(5000, 0.1 kW) with 500 kW charge and discharge limits (33046/33047,
0.01 kW). Use 10 kW and 5 kW, in the register set, the global defaults
and the sungrow-hybrid and residential-5kw profiles.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
The Sungrow model stored an EMS's writes to 13049-13051 and never
applied them, so an EMS under test commanded a battery that did not
move. With POST /api/simulators/{id}/config {"ems_control": true} the
battery does what a real SH does: in forced mode (13049 = 2) it follows
13050 (170 charge, 187 discharge, 204 stop) and 13051 watts; in any
other mode it runs self-consumption against the site meter. It answers
after ems_response_ms (default 2000), stays within 33046/33047 and the
SoC limits 13057/13058, and writes the power-flow flags (13000) the Lua
driver signs the power by. Off by default: the dashboard sets the
battery by writing the registers directly.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
A profile now says which srcfl/device-drivers driver it emulates
(driver_id, the file stem: sungrow, sdm630, pixii, ocpp...) and carries
the model's timing in a model block, so field evidence for a driver can
later set it. command_response_s replaces the two settings this branch
added (ems_response_ms, profile_delay_s): it is how long the device
takes to act on an accepted command, the battery after an EMS write or
the charger after a charging profile. sungrow-hybrid says 2 s; applying
a profile sets it, and POST /api/simulators/{id}/config overrides it.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
…er a queue

Codex's review of #8:
- A Sungrow limit register holding 0 now allows no power that way; before,
  0 turned the clamp off.
- GetCompositeSchedule reports the phases the charger draws on: 16 A on one
  phase, not 5.3 A on three. A change of phases starts a new period.
- A session that starts and ends offline is stopped under the transaction id
  the Central System gives its queued start.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
…10)

* fix(ocpp): one heartbeat and meter loop per connection, DropConnection

Each connection to a Central System started another heartbeat, MeterValues
and simulation loop, and nothing ended them but Stop. After one reconnect
a charger sent every heartbeat and MeterValues twice and integrated its
energy twice a second. Heartbeats and MeterValues now end with their
connection; the simulation runs once for the charger's life, connected
or not, since a car charges through a network outage.

Two hooks for scripted runs: DropConnection(d) closes the connection as a
lost network does and keeps the charger away for d, with the session going
on; SetFrameLog reports every OCPP-J frame the charger reads or writes.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* feat(ocpp): the car's own limits (SetCar)

A car takes at most its own current per phase and charges on its own
phases: a one-phase car under a three-phase order draws on L1 only, and a
car that takes 10 A draws 10 A of a 16 A offer. The charger's offer
(effectivePowerW) is unchanged; its draw follows the car.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* feat(run): headless runs from a house spec, with a timeline and a record

simulator run -spec house.json -port-base N -out DIR builds one house:
devices by the device-drivers driver they emulate (a hybrid whose battery
follows its EMS writes, OCPP chargers with their car), the site meter
behind a fuse per phase, and the house load. It serves them on ports from
the base, applies a timeline of events (loads, pv, soc, plug, car,
offline, online, reconnect, mark, stop), and takes the same events over
POST /api/run/event while it runs. It records a sample a second of what
flows through each fuse, the fuse's damage and each device's state to
plant.jsonl, every OCPP frame per charger, ports.json and result.json.
Self-update endpoints are off in a run.

The site loop read Running without the simulator's lock while a stop
wrote it; it now takes the lock.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(run): an outage asked for during a retry keeps its length; "meter" is reserved

Codex's review of #10:
- A reconnect event while the charger was already waiting to retry only
  moved a deadline nobody read; the retry dialled after the usual delay.
  Each dial now waits out DropConnection's deadline first.
- A device called "meter" lost its ports.json entry to the site meter.
  The spec now refuses that id.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(run): draw port bases below the ephemeral range

freeBase took a base from the kernel's next ephemeral port and skipped
those over 65000. macOS hands ephemeral ports out in turn, so once its
cursor sat near the top every try was skipped and every run test failed
with "no free port range".

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* feat(run): the fuse cabinet's air and a warm start

With the thermal fuse on main (#9), a run's spec can set the cabinet's
air (site.fuse_ambient_c, default 25 °C) and start the fuses warm
(site.fuse_preheat_a, a current per phase they have carried long enough
to settle), as a house is in the evening. A fuse size the profile does
not model is refused before the run touches the simulator's settings.

The site loop now reads its tick before it starts: a run sets the tick
before it builds its site, and the next run could set it again while the
last loop was still reading it (the race detector caught it once runs
followed each other within milliseconds).

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* minor: faults and seeded random timelines for headless runs (#11)

* feat(run): faults and seeded random timelines

Faults for an EMS under test, as events in a headless run and over
/api/run/event: a Modbus device that keeps its connections and answers
nothing (silence), a site meter whose readings stand still (meter_late),
one reading whose total disagrees with its phases (meter_glitch), phase
currents that carry a sign (signed_currents), and a charger's own cap
per phase (load_balancer). New model parameters, overridable per device:
startup_delay_s (the car draws that long after an offer rises from zero)
and load_balancer_a for an OCPP charger, signed_phase_currents for a
meter.

A spec's random block draws a timeline from a seed within the house's
bounds (house load per phase under the fuse less 2 A), picks the open
timing of each device, and writes timeline.json, a spec that replays it.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(run): each session waits out the startup delay; faults keep the latest; a late meter keeps its energy

Codex's review of #11:
- offerSince now resets when a connector leaves its session, so every
  session waits out startup_delay_s, not only the first.
- An earlier silence's or outage's timer no longer ends a later one: each
  device counts its faults and a timer acts only for the latest.
- Energy that flows during meter_late shows on the counters when the
  readings move again; before, it was lost.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* feat(ocpp): a charger wired on one phase

wired_phases: 1 in a run spec (SetWiredPhases) wires a charger on L1. It
gives an order's current there whatever numberPhases says, and max_kw is
its rating as wired, so a 16 A order on a 3.68 kW charger draws 16 A on
L1. Before, the order became 16 A x 3 x 230 W, was capped to 3.68 kW and
spread over three phases, and a one-phase car took 5.3 A of it.

FTW's site test needs it for a charger wired on one phase, under Charge
now and planned charging.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

---------

Co-authored-by: Claude Opus 5.5 <noreply@anthropic.com>

---------

Co-authored-by: Claude Opus 5.5 <noreply@anthropic.com>
@frahlg
frahlg merged commit a3030d3 into main Oct 23, 2026
6 checks passed
@frahlg
frahlg deleted the fix/ftw-rig-gaps branch October 23, 2026 06:04
Sign up for free to join this conversation on GitHub. Already have an account? Sign in to comment

Labels

None yet

Projects

None yet

Development

Successfully merging this pull request may close these issues.

1 participant